Foydalanish doirasi
ZJB seriyali transformator moyi filtrlash moslamasi asosan izolyatsiya moyi, transformator moyining xususiyatlarini yaxshilash uchun ishlatiladi. U izolyatsion tizimga ega bo'lgan transformatorlar, o'chirgichlar, o'zaro induktorlar, kabel va kondensatorlarning ish faoliyatini yaxshilash uchun izolyatsion moy, elektr moy va transformator moyidan suv, gaz, aralashmalar va boshqalarni samarali va tez olib tashlashi mumkin.

Onlayn ish haqida eslatmalar:
Birinchisi - tayyorgarlik:
1. Transformator moyini to'ldirish miqdorining 5-6 foizi bilan malakali yog'ni tayyorlang va uni moy filtri yoniga qo'ying;
2. Transformatorning pastki qismidagi yog 'to'kish valfi porti yog 'filtrining moy kirish trubkasi bilan mos kelishi kerak.
3. Transformator moyini filtrlash moslamasi vakuum tankining moy standart trubasining 1/2 qismidagi malakali moy bilan jihozlangan bo'lishi kerak (bosim qarshiligi qiymati 50KV dan katta yoki unga teng);
4. Transformatorning yog 'yostig'i qopqog'ini oching, yog 'filtrining yog 'chiqishi trubkasini yog' yostig'idagi yog' darajasiga soling va keyin yog' yostig'i qopqog'ini toza filtr qog'ozi yoki plyonka bilan yoping;
5. Yog 'filtrining moy kirish trubkasini malakali moy bilan tayyorlangan yog 'barabaniga soling;
6. Transformatorning pastki qismidagi yog 'to'kish klapanini oching va transformator yog'ining 3-5 foizini to'kib tashlang (3-5 foizli yog 'asosan aralashmalar va suvdir, ularni alohida ulash va tushirish kerak);
7. 6-bosqich bilan bir vaqtda, yog 'filtrini yuqori vakuumga (-0.09MPa dan kam bo'lmagan) aylantirish kerak va transformator moyi yostig'ining yog 'darajasini darhol to'ldirish kerak;
8. When the oil drain valve at the bottom of the transformer discharges 3 to 5 percent of the "waste oil", connect the oil inlet pipe of the oil filter to the oil drain valve;
9. Bu vaqtda transformator moyini filtrlash moslamasi normal ishlashi mumkin.
Texnik spetsifikatsiya
Element | Birlik | ZJB -10 | ZJB -20 | ZJB -30 | ZJB -50 | ZJB -75 | ZJB -100 | ZJB -150 | ZJB-200 | |
Flow rate | L/H | 600 | 1200 | 1800 | 3000 | 4500 | 6000 | 9000 | 12000 | |
Vacuum degree | Mpa | -0.06 -0.098 | ||||||||
Working pressure | Mpa | 0 dan kichik yoki unga teng.4 | ||||||||
Fault free | H | 4000 | ||||||||
Working temperature | daraja | 20-80 | ||||||||
Continuous working time | H | 150 | ||||||||
Power supply | 380V/50Hz (yoki talab bo'yicha) | |||||||||
Shovqin | dB(A) | 75 dan kam yoki teng | 80 dan kam yoki teng | |||||||
Heating power | kVt | 9 | 15 | 18 | 30 | 48 | 60 | 90 | 105 | |
Total power | kVt | 11 | 17 | 21 | 33 | 53 | 65 | 96 | 116 | |
Inletoutlet size | mm | 25 | 25 | 25 | 32 | 40 | 40 | 50 | 60 | |
Og'irligi | Kg | 380 | 400 | 420 | 510 | 550 | 730 | 960 | 1200 | |
Hajmi | L | mm | 1050 | 1150 | 1200 | 1300 | 1600 | 1600 | 2100 | 2200 |
| W | mm | 750 | 800 | 800 | 900 | 1000 | 1200 | 1500 | 1600 | |
| H | mm | 1400 | 1450 | 1500 | 1600 | 1800 | 1850 | 2000 | 2100 | |

Issiq teglar: transformator moy filtrlash moslamasi, Xitoy, etkazib beruvchilar, ishlab chiqaruvchilar, moslashtirilgan, ulgurji, narx